Problem analysis
Due to inappropriate protection management of the
internal/external surface of the copper, large amount of
oxidation, dust and foreign substances were seen.
Consequence
R410a refrigerant is very sensitively react with foreign
substances : Mineral oil and compress oil will not solve
with each other due to different chemical characteristics.
Therefore, wax type materials may clog the hole of
EEV or oil filters.
Standard procedure
Check if it is clean enough.
Foreign substances in the copper pipe < 30mg/10m
R410a copper pipe must be kept clean until it is
installed.
Proper method
Select the clean copper pipes and make sure no dust or
foreign substances get into the
pipe when you keep
them. If the copper pipes are stored for a long period of
time, clean them(blow Nitrogen) before installation to
remove undesired material from inside of the pipe