Installation guide
133
11. Pump-Down Operation
1) General Instructions
(1) Pump-down operation is to gather the refrigerant into outdoor unit.
(2) If system is under extremely low pressure, compressor will be damaged. When low pressure go
down 2kgf/㎠ or below, close the service valve quickly.
2) Procedure of Pump down operation
Close Gas SVC Valve of Sub Unit
Press “K2” button 3 times
for pump down operation
Push “K4” button 4 times for
checking low pressure *1)
- “4” means low pressure view mode
- “0 32” means low pressure is 3.2kgf/㎠g
2kgf/㎠
(of Main Unit)
Press “K2” button 2 times
or “K3” button 1 time
for the end of pump down operation
Press “K2” button 3 times
for pump down operation
Close Liquid SVC Valve of Sub Unit
Close Liquid SVC Valve of Main Unit