E-79
LonWorks Gateway Setting
Centralized
controller
LonWorks Gateway
TP/FT-10
BMS system
BMS Engineering
SAMSUNG Engineering
Interface module
Interface module
Interface module
Connecting centralized controller and LonWorks Gateway ( type)
- You can control up to 16 centralized controllers and 128 indoor units using LonWorks Gateway.
Connecting interface module and LonWorks Gateway( type)
- You can control up to 80 interface modules and 128 indoor units using LonWorks Gateway.
* MAX.16 interface module can be connected to each of the RS485 communication channels of
the LonWorks Gateway.
- The more interface modules are connected, the longer time takes for tracking.
When connecting centralized controller and interface module to the LonWorks
Gateway of same communication channel, only one of them will communicate
according to the communication channel mode setting of [System Settings]-
[Tracking]. Therefore,
do not connect the centralized controller and interface module to the same
communication channel.
If you set the communication channel mode as interface module, virtual centralized
controller address will be assigned. Therefore please aware of that if you set the
centralized controller address as virtual centralized controller address when you
connect interface module and centralized controller at the same, it may cause
trouble for bringing device information.
Channel 0: Virtual centralized controller 11, Channel 1: Virtual centralized controller
12, Channel 2: Virtual centralized controller 13, Channel 3: Virtual centralized
controller 14, Channel 4: Virtual centralized controller 15
System Architecture
SOL_DMS2&BAC&LW_IBIM_EN_32138A-10_EN_150617.indd 79 2015-06-18 오후 5:34:26