E-69
BACnet Gateway setting (Continued)
Single AHU unit has following point list.
Instance
Number
Object
Object
Type
Object Name
Unit Status value
Inactive
Active
Text-1 Text-2 Text-3 Text-4 Text-5
1 Indoor Temperature AI AHU_RoomTemp_xx_xxxxxx °C
2 Set temperature AV AHU_Temp_Set_xx_xxxxxx °C
3
Setting lower temperature
limit
AV AHU_Cool_LimitTemp_xx_xxxxxx °C
4
Setting upper temperature
limit
AV AHU_Heat_LimitTemp_xx_xxxxxx °C
5
The power value of an indoor
unit after the basic date
AI AHU_Baseline_kWh_xx_xxxxxx kWh
6
The number of hours usage
of an indoor unit after the
basic date
AI AHU_Baseline_Minute_xx_xxxxxx
Minute
7 Power value within period AI AHU_Period_kWh_xx_xxxxxx kWh
8
The number of hours usage
of an indoor unit within
period
AI AHU_Period_Minute_xx_xxxxxx
Minute
9 Power On/O BV AHU_Power_xx_xxxxxx O On
10
Applying lower temperature
limit setting
BV AHU_Cool_Limit_set_xx_xxxxxx False True
11
A p p l y i n g u p p e r
temperature limit setting
BV AHU_Heat_Limit_set_xx_xxxxxx False True
12 Filter sign status BI AHU_FilterSign_xx_xxxxxx False True
13 Filter sign reset BO AHU_FilterSign_Reset_xx_xxxxxx False True
14 Operation mode status MV AHU_Operation_Mode_xx_xxxxxx Auto Cool Heat Fan Dry
15
Ope rat ion mo de lim it
status
MV AHU_Mode_Limit_xx_xxxxxx
No
Limit
Cool
Only
Heat Only
16
Remote controller limit
status
MV AHU_Remocon_Limit_xx_xxxxxx
Enable
RC
Disable
RC
Conditional
RC
17
I nte g ra t e d e r r or c od e
of both indoor unit and
outdoor unit
AI AHU_Error_Code_xx_xxxxxx Refer to list of error code
* 18
Di s c ha r g e c oo l i ng s et
temperature
AV AHU_DisCoolSetTemp_xx_xxxxxx °C
* 19
Di s ch ar g e he ati ng se t
temperature
AV AHU_DisHeatSetTemp_xx_xxxxxx °C
* 20
D i s c h a r g e c u r r e n t
temperature
AI AHU_Dis_CurrentTemp_xx_xxxxxx °C
* 21 Humidification setting BV AHU_Humidification_xx_xxxxxx O On
* 22 Outdoor air intake setting BV AHU_OAIntake_xx_xxxxxx O On
* 23 Outdoor cooling setting BV AHU_OutdoorCool_xx_xxxxxx O On
* 24 Fan speed status MV AHU_FanSpeed_xx_xxxxxx Low Mid High
* 25 Set humidity status MV AHU_SetHumidity_xx_xxxxxx Low Mid High
* 26 Current humidity status MI AHU_CurrentHumidity_xx_xxxxxx Low Mid High
27 AHU Notify NC AHU_Notify_xx_xxxxxx
When the error occurred, send event to
list of destination in the recipient_list.
(Max : 8)
(*) Mark is not supported.
AHU Kit
SOL_DMS2&BAC&LW_IBIM_EN_32138A-10_EN_150617.indd 69 2015-06-18 오후 5:34:19