E-67
BACnet Gateway setting (Continued)
BACnet Point List
Single indoor unit has following point list.
Instance
Number
Object
Object
Type
Object Name
Unit Status value
Inactive
Active
Text-1 Text-2 Text-3 Text-4 Text-5
1 Indoor Temperature AI AC_RoomTemp_xx_xxxxxx °C
2 Set temperature AV AC_Temp_Set_xx_xxxxxx °C
3
Setting lower temperature
limit
AV
AC_Cool_LimitTemp_xx_xxxxxx
°C
4
Setting upper temperature
limit
AV
AC_Heat_LimitTemp_xx_xxxxxx
°C
5
The power value of an indoor
unit after the basic date
AI AC_Baseline_kWh_xx_xxxxxx kWh
6
The number of hours usage of
an indoor unit after the basic
date
AI AC_Baseline_Minute_xx_xxxxxx Minute
7 Power value within period AI AC_Period_kWh_xx_xxxxxx kWh
8
The number of hours usage of
an indoor unit within period
AI AC_Period_Minute_xx_xxxxxx Minute
9 Power On/O BV AC_Power_xx_xxxxxx O On
10
Applying lower temperature
limit setting
BV AC_Cool_Limit_set_xx_xxxxxx False True
11
Applying upper temperature
limit setting
BV AC_Heat_Limit_set_xx_xxxxxx False True
12 Filter sign status BI AC_FilterSign_xx_xxxxxx False True
Indoor Unit
SOL_DMS2&BAC&LW_IBIM_EN_32138A-10_EN_150617.indd 67 2015-06-18 오후 5:34:19