E-68
Instance
Number
Object
Object
Type
Object Name
Unit Status value
Inactive
Active
Text-1 Text-2 Text-3 Text-4 Text-5
13 Filter sign reset BO
AC_FilterSign_Reset_xx_xxxxxx
False True
14 Operation mode status MV AC_Operation_Mode_xx_xxxxxx Auto Cool Heat Fan Dry
15 Fan speed status MV AC_FanSpeed_xx_xxxxxx Auto Low Mid High
16 Air ow direction status MV AC_FanFlow_xx_xxxxxx
None Vertical Horizon All
17 Operation mode limit status MV AC_Mode_Limit_xx_xxxxxx
No Limit Cool Only Heat Only
18 Remote controller limit status MV
AC_Remocon_Limit_xx_xxxxxx
Enable RC Disable RC
Conditional
RC
19
Integrated error code of both
indoor unit and outdoor unit
AI AC_Error_Code_xx_xxxxxx Refer to list of error code
* 20 SPI setting BV AC_SPI_xx_xxxxxx False True
* 21 HumanSensor setting BV AC_MDS_xx_xxxxxx False True
22 AC Indoor Notify NC AC_Notify_xx_xxxxxx
When the error occurred, send event to list of
destination in the recipient_list. (Max : 8)
Temperature setting range can be different depending on the model and the common range is as fol-
lows:
Auto: 18˚C~30˚C
Cool: 18˚C~30˚C
Heat: 16˚C~30˚C
Fan: Temperature cannot be adjusted
Dry: 18˚C~30˚C
(*) Mark is optionally supported.