E-71
BACnet Gateway setting (Continued)
Single ERV unit has following point list.
Instance
Number
Object
Object
Type
Object Name
Unit Status value
Inactive
Active
Text-1 Text-2 Text-3 Text-4 Text-5
1 Power On/O operation BV ERV_Power_xx_xxxxxx Off On
2 Filter sign status BI
E R V _ Fi l t e r S i g n _ x x _
xxxxxx
False True
3 Filter sign reset BO
ERV_FilterSign_Reset_
xx_xxxxxx
False True
4 Operation mode status MV
ERV_Operation_Mode_
xx_xxxxxx
Auto HeatEx Bypass Sleep
5 Fan speed status MV
E R V _ F a n S p e e d _x x _
xxxxxx
Low High Turbo
6
Remote controller limit
status
MV
ERV_Remocon_Limit_
xx_xxxxxx
Enable
RC
Disable
RC
Conditional RC
7
Integrated error code of
ERV unit
AI
ERV_Error_Code_xx_
xxxxxx
Refer to list of error code
8 ERV Notify NC ERV_Notify_xx_xxxxxx
When the error occurred, send event to list of
destination in the recipient_list. (Max : 8)
ERV
Instance
Number
Object
Object
Type
Object Name
Unit Status value
Inactive
Active
Text-1 Text-2 Text-3 Text-4
25 On/Off status of hot water mode BV EHS_HotWater_Power_xx_xxxxxx Off On
26 Status of quiet operation BV EHS_Sleep_xx_xxxxxx Off On
27 Operation mode status MV EHS_Operation_Mode_xx_xxxxxx Auto Cool Heat
28 Operation mode limit status MV EHS_Mode_Limit_xx_xxxxxx No Limit Cool Only Heat Only
29 Remote controller limit status MV EHS_Remocon_Limit_xx_xxxxxx
Enable RC
Disable RC
Conditional
RC
30
Status of hot water operation
mode
MV EHS_HotWater_Mode_xx_xxxxxx Force Eco Standard Power
31
Integrated error code of both in-
door unit and outdoor unit
AI EHS_Error_Code_xx_xxxxxx
32 EHS notifiy NC EHS_Notify_xx_xxxxxx
When the error occurred, send event to list of
destination in the recipient_list. (Max : 8)
SOL_DMS2&BAC&LW_IBIM_EN_32138A-10_EN_150617.indd 71 2015-06-18 오후 5:34:19