Main Function
PEAK power management is operating in ‘No PEAK setup, ‘Priority control mode’, or
‘Circulation control mode’.
No PEAK setup: This is a factory default and the PEAK power management is not in
operation.
Priority control mode: PEAK power operation mode that assigns indoor units to Levels
1,2 and 3 or none and operates the respective indoor units when the power level at
the peak interface module reaches anyone of the preset level.
Priority of each indoor units can be set through the Web or with Upper level controller.
Operational modes
PEAK level
Applied group
Level 0 No Peak power management
Level 1 Peak power management on groups within priority level 1 group
Level 2 Peak power management on groups within priority level 1 and 2
Level 3
Peak power management on groups within priority level 1~3
Circulation control mode: An energy saving function that operates each class in
rotation according to the alert level at the peak interface module. The higher the alert
level, the more classes will be put on energy-saving operation.
Within the set Circulation period, indoor units in applied group will be restricted in
its operation. When the Circulation period ends, next applied group will be restricted
since PEAK power management will be active, and the indoor units in previous group
will operate in the recent mode used.
PEAK level
Applied group
Level 0 No Peak power management
Level 1 Peak power management on groups within priority level 1 group
Level 2 Peak power management on groups within priority level 1 and 2
Level 3
Peak power management on groups within priority level 1~3