10) Property support specification
(1) Device property
Property identifier Property data
Check
code
Support
DMS2
1 Object identifier BACnetObjectIdentifier R V Individual identifier
2 Object name CharaterString R V
SAMSUNG DVM
Gateway
3 Object type BACnetObjectType R V DEVICE
4 System status BACnetDeviceStatus R V
During communication:
“OPERATIONAL”
Error with DMS2:
“NON_OPERATIONAL”
5 Vendor name CharacterString R V
Samsung Electronics
CO., Ltd.
6 Vendor identifier Unsigned16 R V 200
7 Model name CharterString R V MIM-B17N
8 Firmware revision CharterString R V 1.00
9 Application software version CharterString R V 1.00
10 Location CharterString O X
11 Description CharterString O V
DMS2_BACnetIP
[ver 1.00]
12 Protocol version Unsigned R V 1.00
13 Protocol conformance class Unsigned(1..6) R X
14 Protocol services supported BACnetServicesSupported R V For each device
15 Protocol object types supported BACnetObjectTypesSupported R V For each device
16 Object list
BACnetidentifier BACnet sequence [N]
R V For each device
17 Max APDU length accepted Unsigned R V 1476
18 Segmentation supported BACnetSegmentation R V NO-SEGMENTATION
19 VT classes supported BACnetVTClass O
(1)
X
20 Active VT sessions BACnetVTSessions O
(1)
X
21 Local time Time O V Supported
22 Local date Date O V Supported
23 UTC offset INTEGER O X
24 Daylight savings timeout BOOLEAN O X
25 APDU segment timeout Unsigned O
(2)
X
26 APDU timeout Unsigned R V 3000
27 Number of APDU retries Unsigned R V 3
28 List of session keys BACnetSessionKey O X
29 Time synchronization recipients BACnetRecipient O
(3)
X
30 Max master Unsigned(1..127) O
(4)
VX
31 Max info frames Unsigned O
(4)
VX
32 Device address binding BACnetAddressBinding R V X
33 Protocol revision Unsigned R V 2