Wiring Work
Rating current
Unit Model Rating current
AVXC1
022
028
036
0.18A
0.20A
0.23A
AVXCS
022
028
036
0.20A
0.23A
0.25A
AVXC2
056
071
0.38A
0.40A
AVXC4E
045
056
071
090
112
128
140
0.19A
0.19A
0.21A
0.23A
0.23A
0.30A
0.36A
AVXC4EG
045
056
071
090
112
128
140
0.40A
0.40A
0.40A
0.50A
0.60A
0.60A
0.80A
AVXCM
028
036
056
071
0.50A
0.50A
0.52A
0.55A
Specification of electronic wire
Power supply MCCB ELB Power cable Earth cable
Communication
cable
Max : 242
V
Min : 198V
X A
X A, 30mmA
0.1 sec
2.5mm
2
2.5mm
2
0.75~1.5mm
2
Decide the capacity of ELB and MCCB by below formula.
The capacity of ELB, MCCB X [A] = 1.25 X 1.1 X
∑
Ai
X
: The capacity of ELB, MCCB
∑
Ai : Sum of Rating currents of each indoor unit.
Refer to each installation manual about the rating current of indoor unit.
Decide the power cable specification and maximum
length within 10% power drop among indoor units.
Coef: 1.55
Lk: Distance among each indoor unit[m], Ak: Power cable specification[mm
2
]
i
k: Running current of each unit[A]
∑ (
Coef
×35.6×Lk×ik
) <
10% of input
voltage[V]
1000×Ak
n
k=1
Example of Installation
- Total power cable length L = 100(m), Running current of each units 1[A]
- Total 10 indoor units were installed
10[A]
Indoor unit10
20[m]10[m]0[m]
9[A] 1[A]
100[m]
MCCB
Indoor unit
2Indoor unit1
ELB
Apply following equation.
∑ (
Coef
×35.6×Lk×ik
) <
10% of input
voltage[V]
1000×Ak
n
k=1
Calculation
Installing with 1 sort wire.
220[V]
-2.
2[V] -2.0[V]
············ 2.5[mm
2
] ············
208.8[V](Within 198V~242V)
-(2.2+2.0+1.8+1.5+1.3+1.1+0.9+0.7+0.4+0.
2)=-11.2[V]
it's okay
2.5[mm
2
] 2.5[mm
2
]
Installing with 2 different sort wire.
220[V]
-1.4[V] -1.2[V]
············ 2.5[mm
2
] ············
209.5[V](Within 198V~242V)
-(1.4+1.2+1.8+1.5+1.3+1.1+0.9+0.7+0.4+0.2
)=-10.5[V]
it's okay
4.0[mm
2
] 4.0[mm
2
]