Samsung MIM-B17C Especificaciones Pagina 43

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 67
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 42
Troubleshooting
5-15 Samsung Electronics
5-2-14. When the BACnet is Not Connecting
Check the condition of Ethernet cable
Start
Yes
No
Is the cable for Ethernet
proper?
Yes
Yes
No
Are the addresses for
Ethernet correct?
Check the condition of Ethernet
connector
Yes
No
Is the connector for Ethernet
proper?
Change Main Board
No
Are the static LEDs for Ethernet proper?
(Ethernet Linked, Ethernet Active)
No
Is the device instance
number for BACnet correct?
Yes
Yes
Check IP, Subnet mask and gateway address
(Refer to install and service manual)
Linked : Constant
Active : Flickering
Check Device Instance number
End
Change Main Board
BACnet Gateway_E_32400A(1)_1.indd 15 2010-05-17 �� 10:35:02