6
Console
X Ratings shown are net capacities.
X Capacities are based on following conditions;
- Equivalent refrigerant piping length : 5m / Level difference : 0m.
;
Note
6-2. Capacity tables
3) JH052EAV1
(1) Cooling
Indoor
Temperature(°C)
Outdoor Temperature (°C, DB)
-15 -10 21 35 43
WB DB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14 20
4.41 3.19 0.94 4.76 3.42 0.95 5.22 3.73 1.34 4.44 3.08 1.56 4.58 3.07 2.39
16 22
4.73 3.19 0.98 5.00 3.37 0.95 5.47 3.67 1.34 4.67 3.03 1.56 4.83 3.04 2.43
18 25
4.93 3.34 0.98 5.23 3.54 0.98 5.74 3.86 1.34 4.89 3.18 1.56 5.06 3.19 2.43
19 27
5.03 3.52 0.98 5.33 3.73 0.98 5.87 4.10 1.34 5.00 3.38 1.56 5.18 3.39 2.43
22 30
5.33 3.38 1.00 5.68 3.60 0.98 6.26 3.97 1.36 5.33 3.27 1.58 5.53 3.28 2.43
24 32
5.54 3.29 1.00 5.90 3.50 0.99 6.50 3.86 1.36 5.57 3.20 1.58 5.78 3.21 2.47
(2) Heating
Indoor
Temperature(°C)
Outdoor Temperature (°C, DB)
-20 -10 -5 2 7 24
DB TC PI TC PI TC PI TC PI TC PI TC PI
16
3.29 2.03 5.22 2.42 5.39 2.28 5.71 2.28 5.76 1.51 4.62 1.51
18
3.53 2.06 5.09 2.46 5.29 2.39 5.65 2.30 5.68 1.53 4.56 1.51
20
3.67 2.09 4.97 2.49 5.21 2.41 5.55 2.30 5.60 1.55 4.51 1.53
21
3.75 2.09 4.93 2.49 5.15 2.41 5.51 2.34 5.57 1.55 4.47 1.55
22
3.98 2.09 4.86 2.49 5.11 2.44 5.45 2.34 5.52 1.55 4.45 1.55
24
4.14 2.12 4.77 2.53 5.00 2.48 5.38 2.36 5.45 1.56 4.39 1.57
TC(Total Capacity, kW), SHC(Sensible Heat Capacity, kW), PI(Power Input, kW)
TC(Total Capacity, kW), PI(Power Input, kW)